64 CSI Section 16470
Siemens Electrical Products and Systems
Specification Guide
Tie Breaker Sections and Combinations — Front Views
480V Metal-Enclosed Switchgear
Auxiliary / Breaker Section Dimensions
Dimensions
480V Metal-Enclosed
Switchgear
4
R30R22
Indoor
Outdoor
1000 (455) 1200 (545)
2000 (909) 2400 (1091)
Table 4.21
Weight in lbs. (kg)
Auxiliary Section
Auxiliary Sections — Front Views
R30R22
Indoor
Outdoor
1400 (636) 1900 (864)
2400 (1091) 3100 (1409)
R36
2210 (1005)
Table 4.22
Connection Weights in lbs. (kg)
Breaker Section and
Weights shown do not include weight of circuit breaker
removeable elements. All weights are approximate
based on aluminum bus. For outdoor lineup, add
1200 lb (545 kg) to total weight of individual sections for
end walls and hoist.
Main Breaker Sections — Front Views
Feeder Breaker Sections and Combinations — Front Views
Breaker Designations
A = RL- 800 / 1600 / 2000,
RLF- 800 / 1600 / 2000,
RLE- 800 / 2000
, RLI-800
B = RL- 3200
C = RLF- 3200 in one cell, with
fuse drawout (RFC-3200)
in other cell
D = RLF- 4000 in one cell, with
fuse drawout (RFC-4000)
in other cell
E = RL- 4000, RLE-4000
F = RLF- 5000 in one cell with
fuse drawout (RFC-5000)
in other cell
G = RL- 5000
22 in. (559 mm) compartment only.
Feeder breakers located above tie breaker must be
electrically on opposite side of tie breaker from
feeder breaker which is located below the breaker.
Dimensions in Inches (mm)