Modbus Slave Module #4 Links
Measurement Label Source
Module
Modbus Module and Input
Number
Modbus
Register
Imported kWh kWh imp Integrator Modbus Slave #4 – Source Input #1 40089-40090
Exported kWh kWh exp Integrator Modbus Slave #4 – Source Input #2 40091-40092
Total kWh kWh tot Integrator Modbus Slave #4 – Source Input #3 40093-40094
Net kWh kWh net Integrator Modbus Slave #4 – Source Input #4 40095-40096
Imported kVARh kVARh imp Integrator Modbus Slave #4 – Source Input #5 40097-40098
Exported kVARh kVARh exp Integrator Modbus Slave #4 – Source Input #6 40099-40100
Total kVARh kVARh tot Integrator Modbus Slave #4 – Source Input #7 40101-40102
Net kVARh kVARh net Integrator Modbus Slave #4 – Source Input #8 40103-40104
Total kVAh kVAh Integrator Modbus Slave #4 – Source Input #9 40105-40106
Max Phase A Voltage THD V1 THD max Maximum Modbus Slave #4 – Source Input #10 40107-40108
Max Phase B Voltage THD V2 THD max Maximum Modbus Slave #4 – Source Input #11 40109-40110
Max Phase C Voltage THD V3 THD max Maximum Modbus Slave #4 – Source Input #12 40111-40112
Max Phase A Current THD I1 THD max Maximum Modbus Slave #4 – Source Input #13 40113-40114
Max Phase B Current THD I2 THD max Maximum Modbus Slave #4 – Source Input #14 40115-40116
Max Phase C Current THD I3 THD max Maximum Modbus Slave #4 – Source Input #15 40117-40118
Importing Data using Modbus RTU
It is possible to bring data into the 9700 Power Meter using Modbus.
Various registers can be written by Modbus Master devices by correlating
the Modbus register number with the address of the register you want to
write. When a Modbus register is written with a value, the corresponding
register will be written, provided the Modbus RTU protocol is active on the
communications channel that connects the Modbus Master to the 9700
Power Meter.
You can use the Modbus RTU protocol to write values into external numeric,
pulse and Boolean registers, allowing you to enable, disable and reset 9700
Power Meter functions. You can also use the Modbus protocol to change
setup register values in various modules to configure the 9700 Power
Meter’s operation.