Module Summary Table, Continued
Module
Name
Total
Available
in 7700
Used in
Factory
Config.
High-
Speed
Capable
Setup Registers Range or Options Creation Default
AIChangeEvents
• 32-Bit Analog Change
Event Without Time
• 32-Bit Analog Change
Event With Time
• 16-Bit Analog Change
Event Without Time
• 16-Bit Analog Change
Event With Time
16-Bit Analog Change
Event Without Time
AIChangeEvDepth 100 to 200 200
AOStatic 32-bit Analog Output
Status/
16-bit Analog Output
Status
16-bit Analog Output
Status
SelectTimeout 0-10 seconds 10 seconds
TimeSynchPeriod 1- 86400 seconds (1 day) 86400
ALFragSize 15 – 2048 bytes 2048
DLAck ALWAYS, MULTI-PACKET
ONLY, NEVER
NEVER
DLTimeout 100 msecs to 10 seconds 2 seconds
DNP Slave
Options *
continued
Note: DNP
is only
available on
Com 2 or
Com 3
111
DLNumRetries 0-10 0
Gateway
valid IP address
SubnetMask
valid IP address
IP Address
valid IP address
Ethernet * 1 1 none
Protocol SEAbus or MODBUS RTU SEAbus
Depth 0 to 20 000 500
Protection The Protection register is factory-set to 128.
Event Log
Controller *
11N/A
Cutoff 0 to 255 5
External
Boolean
32 11 0 EvPriority 0 to 127 0
External
Numeric
20 5 0 EvPriority 0 to 127 0
External
Pulse
128 17 0 EvPriority 0 to 127 0
Device Type
(read-
only)
N/A 9700 Power MeterFactory * 1 1 N/A
Compliance
(read-
only)
N/A SEAbus-Compliant
* denotes Core module (refer to chapter 4)